Agency | Comment | ||
---|---|---|---|
PCD Project Manager
3/3/2021 7:56:23 AM |
Planning Division has no further comments at this time. | 3/3/2021 7:56:23 AM | |
EPC Stormwater Review
3/2/2021 8:10:31 AM |
Stormwater has no additional comments. | 3/2/2021 8:10:31 AM | |
PCD Engineering Division
3/1/2021 5:44:29 PM |
Engineering comments have been resolved. Staff has contacted the engineer regarding a missing signature on the FAE. The engineering documents will be uploaded once approved by the ECM Administrator. reviewed by: Daniel Torres danieltorres@elpasoco.com |
3/1/2021 5:44:29 PM | |
County Attorney - Development Review
2/23/2021 4:27:50 PM |
No further comments. | 2/23/2021 4:27:50 PM | |
View |
PCD Project Manager
2/11/2021 5:15:46 PM |
PCD Engineering comments on drainage report attached. | 2/11/2021 5:15:46 PM |
View |
PCD Project Manager
2/11/2021 5:15:08 PM |
PCD Engineering and EPC Stormwater comments on construction drawings attached. | 2/11/2021 5:15:08 PM |
PCD Engineering Division
2/11/2021 2:17:01 PM |
Review 3 comments on the following documents will be uploaded by the project manager: -Drainage Report: minor comments -Construction Drawings: minor comments Engineering comments on the following documents have been resolved -FAE -Site Development Plan Please submit signed engineering documents by the engineer and developer for approval by the ECM administrator. Ryan: A 1 week turnaround would be acceptable. reviewed by: Daniel Torres danieltorres@elpasoco.com |
2/11/2021 2:17:01 PM | |
PCD Project Manager
2/10/2021 2:18:31 PM |
Planning Division has no further comments at this time. Documents from Stormwater and Engineering review will be uploaded when Engineering Division has completed its review. | 2/10/2021 2:18:31 PM | |
EPC Stormwater Review
2/10/2021 11:30:19 AM |
Review 3: EPC Stormwater comments have been provided on the following uploaded documents: - Construction Drawings (to be uploaded by PM with PCD comments) Please sign and resubmit the following documents: - GEC Checklist (you uploaded the FDR checklist in its place) - SWMP Checklist Stormwater comments have been resolved on the following documents: - ESQCP Reviewed by: Christina Furchak Stormwater Engineer III christinafurchak@elpasoco.com |
2/10/2021 11:30:19 AM | |
View |
County Attorney - Development Review
2/9/2021 3:26:51 PM |
Proposed changes to Detention Maintenance Agreement are attached. If acceptable, please accept all changes, remove Exhibit B (unnecessary), and submit final draft for final review. | 2/9/2021 3:26:51 PM |
View |
PCD Project Manager
1/8/2021 10:11:25 AM |
GEC checklist comments attached. Includes EPC Stormwater comments. | 1/8/2021 10:11:25 AM |
View |
PCD Project Manager
1/8/2021 10:11:02 AM |
ESQCP comments attached. Includes EPC Stormwater comments. | 1/8/2021 10:11:02 AM |
View |
PCD Project Manager
1/8/2021 10:10:37 AM |
Construction drawing comments attached. Includes EPC Stormwater comments. | 1/8/2021 10:10:37 AM |
View |
PCD Project Manager
1/7/2021 5:23:52 PM |
Site development plan comments attached. Also includes PCD Engineering comments. | 1/7/2021 5:23:52 PM |
View |
PCD Project Manager
1/7/2021 5:23:28 PM |
Lighting plan comments attached. | 1/7/2021 5:23:28 PM |
View |
PCD Project Manager
1/7/2021 5:23:12 PM |
Letter of Intent comments attached. | 1/7/2021 5:23:12 PM |
View |
PCD Project Manager
1/7/2021 5:22:27 PM |
Landscape plan comments attached. | 1/7/2021 5:22:27 PM |
View |
PCD Project Manager
1/7/2021 5:22:06 PM |
Financial assurance form comments attached. Includes PCD Engineering comments. | 1/7/2021 5:22:06 PM |
View |
PCD Project Manager
1/7/2021 5:21:20 PM |
Drainage report comments attached. Includes PCD Engineering comments. | 1/7/2021 5:21:20 PM |
PCD Engineering Division
1/7/2021 2:37:55 PM |
Comments were made on the following documents and will be uploaded by the Project Manager. Steve Kuehster PCD Engineering: Final Drainage Report Version 2. Site Development Plan Version 2. Financial Assurance Estimate. The Applicants Engineer is advised to review the Version One review letter for the Final Drainage Report Checklist and ensure the next submittal meets all the items called out on the check list as well as the review comments. |
1/7/2021 2:37:55 PM | |
County Attorney - Development Review
1/6/2021 3:38:06 PM |
The Detention Maintenance Agreement provided is a City of Colorado Springs document. Please obtain the correct County template from the County project manager, edit and fill out to fit this particular project, add appropriate exhibits, and submit in Word for review. | 1/6/2021 3:38:06 PM | |
View |
EPC Stormwater Review
12/29/2020 12:47:40 PM |
ESQCP_v2 | 12/29/2020 12:47:40 PM |
View |
EPC Stormwater Review
12/29/2020 12:47:10 PM |
GEC Checklist_v2 | 12/29/2020 12:47:10 PM |
EPC Stormwater Review
12/29/2020 12:46:28 PM |
Review 2: EPC Stormwater comments have been provided on the following uploaded documents: - Construction Drawings (to be uploaded by PM with PCD comments) - GEC Checklist - ESQCP Stormwater comments have been resolved on the following documents: - PBMP Applicability Form - SWMP Reviewed by: Christina Furchak Stormwater Engineer III christinafurchak@elpasoco.com |
12/29/2020 12:46:28 PM | |
Pikes Peak Regional Building Department
12/22/2020 4:47:25 PM |
In my comments on 11-1920, I stated that the barn needed to be converted from residential to commercial. The plan has been submitted for the barn as a barn w/loft is 12740 Black Forest Road. Plan R125629 & permit M78797. The intent letter states that the future barn is to be re-purposed in use as a studio/shop to support corporate functions of the company roof specialties. This seems to be commercial and not residential. The permit and the plan are for residential. You will have to do a change of occupancy from a residential U to a commercial B/S (?) before you can use it for any part of the business function. Please clarify the intent. Main building Metal Roof Innovations, Ltd. address is 12738 Black Forest Road. Amy Vanderbeek Enumerations Plans Examiner Pikes Peak Regional Building Department O: 719-327-2930 |
12/22/2020 4:47:25 PM | |
County Attorney - Development Review
12/11/2020 4:24:03 PM |
1. With respect to the Detention Maintenance Agreement, the comment dated Oct. 14 has not been addressed. 2. This application is subject to the El Paso County Road Impact Fee. The Fee is due at the time of building permit. The fee applicable to Office uses is currently $3,372 / 1,000 sq. ft., resulting in an estimated fee of $25,795.80. If the applicant elects to join a Public Improvement District with either a 5-mil or a 10-mil mill levy, the amount of the fee due up front would decrease. |
12/11/2020 4:24:03 PM | |
Black Forest Land Use Committee
10/29/2020 5:47:16 AM |
The Black Forest Land Use Committee has no concerns with this plot plan and recommends approval. | 10/29/2020 5:47:16 AM | |
View |
PCD Project Manager
10/23/2020 9:19:44 AM |
Vicinity Location Map V1 Redlines | 10/23/2020 9:19:44 AM |
View |
PCD Project Manager
10/23/2020 9:19:27 AM |
Site Development Plan V1 Redlines | 10/23/2020 9:19:27 AM |
View |
PCD Project Manager
10/23/2020 9:18:32 AM |
Sign Plan V1 Redlines | 10/23/2020 9:18:32 AM |
View |
PCD Project Manager
10/23/2020 9:18:08 AM |
Lighting Plan V1 Redlines | 10/23/2020 9:18:08 AM |
View |
PCD Project Manager
10/23/2020 9:17:43 AM |
Letter of Intent V1 Redlines | 10/23/2020 9:17:43 AM |
View |
PCD Project Manager
10/23/2020 9:17:28 AM |
Landscape Plan drawings V1 Redlines | 10/23/2020 9:17:28 AM |
View |
PCD Project Manager
10/23/2020 9:17:11 AM |
Application Petition Form V1 Redlines | 10/23/2020 9:17:11 AM |
View |
PCD Engineering Division
10/22/2020 2:25:07 PM |
See Attached Comment Letter. PCD Engineering, Steve Kuehster, 719-520-6813 Cursory redlines made on the FDR and Site Development plan. |
10/22/2020 2:25:07 PM |
View |
EPC Stormwater Review
10/22/2020 10:09:22 AM |
SWMP Checklist_V1 | 10/22/2020 10:09:22 AM |
View |
EPC Stormwater Review
10/22/2020 10:08:48 AM |
SWMP_V1 | 10/22/2020 10:08:48 AM |
View |
EPC Stormwater Review
10/22/2020 10:08:26 AM |
PBMP Applicability Form_V1 | 10/22/2020 10:08:26 AM |
View |
EPC Stormwater Review
10/22/2020 10:07:51 AM |
ESQCP_V1 | 10/22/2020 10:07:51 AM |
View |
EPC Stormwater Review
10/22/2020 10:07:22 AM |
GEC Checklist_V1 | 10/22/2020 10:07:22 AM |
EPC Stormwater Review
10/22/2020 10:01:59 AM |
Review 1: EPC Stormwater comments have been provided (in orange text boxes) on the following uploaded documents: - GEC (to be uploaded by PM with PCD comments) - GEC Checklist - ESQCP - PBMP Applicability Form - SWMP - SWMP Checklist Please provide the following documents for review: - Construction Drawings - Financial Assurance Estimate - MS4 Post Construction Form - SDI Reviewed by: Christina Furchak Stormwater Engineer III christinafurchak@elpasoco.com |
10/22/2020 10:01:59 AM | |
Pikes Peak Regional Building Department
10/15/2020 4:06:30 PM |
1. The barn was not permitted through Regional Building Department. Assuming is was considered at the time a residential agricultural building and did not require a review and permit from RBD. Please clarify. This building will need to be converted to commercial use and will require a separate address, since it is being used for commercial use. 2. All free standing signs will be assigned a separate address an permit. Amy Vanderbeek Enumerations Plans Examiner Pikes Peak Regional Building Department O: 719-327-2930 E: Amy@pprbd.org W: 719-327-2953 |
10/15/2020 4:06:30 PM | |
County Attorney - Development Review
10/14/2020 8:34:57 PM |
The submitted Detention Maintenance Agreement is simply the approved template. Please edit and fill in the blanks to fit this particular project, attach proposed exhibits, and resubmit in Word. | 10/14/2020 8:34:57 PM | |
View |
EPC Environmental Services
10/7/2020 3:37:52 PM |
10/7/2020 3:37:52 PM | |
View |
Mountain View Electric Association, Inc.
10/5/2020 2:48:39 PM |
10/5/2020 2:48:39 PM | |
Academy SD 20 Building Fund
10/5/2020 7:27:40 AM |
Academy District 20 is in receipt of File# PPR2023. The district has no comment regarding the requested rezoning of 12740 Black Forest Road for commercial development. If you need additional information, please contact me. Don Smith Planning Consultant 719-234-1222 |
10/5/2020 7:27:40 AM |