Project Review Comments
- Project Name
- Volmer-Volmer Tap kV Transmission Substation SDP
- Description
- A request to develop a 115 kV Transmission Line and substation ( which contains two (2) 12.5kV transformers/115kV transmission lines & associated electric equipment)
- Location
- Parcels
- 5200000251 5200000251 5200000321 5200000321 5200000323 5200000323 5200000324 5200000324 5200000362 5200000362
- Applicant
-
Mountain View Electric Assocation Inc.
Chris Ansari ( chris.ansari@tristategt.org ) Chris Ansari ( chris.ansari@tristategt.org ) - EA Number
- EA17195
- File Number
- PPR2147
- Project Manager
- Kylie Bagley
- Status
- Active
- Created
- 7/24/2020 7:31:24 AM
View: Project Documents
Agency | Comment | ||
---|---|---|---|
View |
EPC Stormwater Review
10/29/2024 4:35:45 PM |
O&M Manual | 10/29/2024 4:35:45 PM |
County Attorney - Development Review
10/29/2024 1:06:38 PM |
Please address prior comments to DMA and upload an updated version. Reviewed by: Erika Keech, Senior County Attorney, erikakeech2@elpasoco.com, 719-520-7013 |
10/29/2024 1:06:38 PM | |
PCD Project Manager
10/29/2024 8:49:20 AM |
No further planning comments | 10/29/2024 8:49:20 AM | |
PCD Engineering Division
10/29/2024 8:30:12 AM |
Review 1 comments remain unresolved. Reviewed By: Lupepackman@elpasoco.com |
10/29/2024 8:30:12 AM | |
EPC Stormwater Review
10/29/2024 4:39:56 PM |
Review 6: EPC DPW Stormwater comments have been provided (in orange text boxes) on the following uploaded documents: - CDs (see previous review comments, the CDs were not resubmitted with Submittal 6) - Drainage Report (see previous review comments, the DR was not resubmitted with Submittal 6) - O&M Manual EPC DPW Stormwater comments have been resolved on the following documents: - Detention Maintenance Agreement Note: Please address County Attorney comments on the DMA and return signed. Reviewed by: Mikayla Hartford Stormwater Engineer I 719.339.5053 MikaylaHartford@elpasoco.com |
10/29/2024 4:39:56 PM | |
View |
County Attorney - Development Review
10/3/2024 2:20:15 PM |
See attached DMA. Reviewed by: Erika Keech, Senior County Attorney, erikakeech2@elpasoco.com, 719-520-7013. |
10/3/2024 2:20:15 PM |
View |
EPC Stormwater Review
9/17/2024 4:39:19 PM |
O&M Manual | 9/17/2024 4:39:19 PM |
View |
EPC Stormwater Review
9/17/2024 4:39:01 PM |
Drainage Report | 9/17/2024 4:39:01 PM |
View |
EPC Stormwater Review
9/17/2024 4:38:46 PM |
Detention Maintenance Agreement | 9/17/2024 4:38:46 PM |
View |
EPC Stormwater Review
9/17/2024 4:36:08 PM |
CDs | 9/17/2024 4:36:08 PM |
EPC Stormwater Review
9/17/2024 4:18:08 PM |
Review 5: EPC DPW Stormwater comments have been provided (in orange text boxes) on the following uploaded documents: - CDs - Detention Maintenance Agreement - Drainage Report - O&M Manual Reviewed by: Glenn Reese, P.E. Stormwater Engineer III 719.675.2654 GlennReese@elpasoco.com |
9/17/2024 4:18:08 PM | |
PCD Project Manager
9/17/2024 12:38:41 PM |
no comments at this time | 9/17/2024 12:38:41 PM | |
View |
PCD Engineering Division
9/17/2024 10:22:38 AM |
CD Redlines PCD | 9/17/2024 10:22:38 AM |
PCD Engineering Division
9/17/2024 10:13:28 AM |
Review 1 comments for the following documents will be uploaded: -CDs Reviewed By: Lupe Packman lupepackman@elpasoco.com |
9/17/2024 10:13:28 AM | |
PCD Project Manager
2/8/2022 11:50:42 AM |
Planning division has no additional comments | 2/8/2022 11:50:42 AM | |
PCD Engineering Division
2/7/2022 11:17:20 AM |
All PCD Engineering comments have been resolved. The project manager will upload any approved documents. Reviewed By: Lupe Packman Review Engineer lupepackman@elpasoco.com |
2/7/2022 11:17:20 AM | |
EPC Stormwater Review
2/4/2022 5:22:59 PM |
Review 4: EPC Stormwater has no further comments at this time. Thanks. Reviewed by: Glenn Reese, P.E. Stormwater Engineer II glennreese@elpasoco.com |
2/4/2022 5:22:59 PM | |
PCD Project Manager
1/27/2022 8:19:05 AM |
No further planning comments | 1/27/2022 8:19:05 AM | |
PCD Engineering Division
1/26/2022 2:32:55 PM |
All PCD Engineering comments have been resolved. Please submit the following engineering documents with the appropriate stamps/signatures when all engineering comments (PCD and EPC Stormwater) have been resolved: -Drainage report -GEC plan and checklist -FAE -SWMP and checklist -PBMP app form -ESQCP Note to the planner: Please set review cycle to 5 days. Reviewed by: Lupe Packman Review Engineer lupepackman@elpasoco.com |
1/26/2022 2:32:55 PM | |
EPC Stormwater Review
1/25/2022 9:46:18 PM |
Review 3: EPC Stormwater comments have been resolved on the following documents: - Drainage Report - GEC Plan - GEC Checklist Once all comments have been resolved from all agencies, please sign, date, and/or stamp the following docs as needed and resubmit: - Drainage Report - GEC Plan EPC Stormwater has no further comments at this time. Thanks. Reviewed by: Glenn Reese, P.E. Stormwater Engineer II glennreese@elpasoco.com |
1/25/2022 9:46:18 PM | |
View |
PCD Project Manager
1/4/2022 5:25:13 PM |
PCD Engineering and EPC Stormwater comments - grading & erosion control plan | 1/4/2022 5:25:13 PM |
View |
PCD Project Manager
1/4/2022 5:23:38 PM |
PCD Engineering comments - financial assurance forms | 1/4/2022 5:23:38 PM |
View |
PCD Project Manager
1/4/2022 5:22:50 PM |
PCD Engineering and EPC Stormwater comments - drainage report | 1/4/2022 5:22:50 PM |
PCD Engineering Division
1/4/2022 5:07:55 PM |
Review 2 comments will be uploaded by the project manager. Please address comments on the following documents: -Drainage report -Financial assurance form -GEC plan Reviewed by: Lupe Packman Review Engineer lupepackman@elpasoco.com |
1/4/2022 5:07:55 PM | |
View |
EPC Stormwater Review
1/4/2022 4:50:37 PM |
GEC Checklist | 1/4/2022 4:50:37 PM |
PCD Project Manager
1/4/2022 3:51:34 PM |
Planning Division has the following comment on the lighting plan: Per LDC Sec. 6.2.3.B.2 Height. No freestanding light fixtures shall be mounted higher than 15 feet, except parking lot light fixtures which shall be mounted no higher than 20 feet unless an alternative lighting proposal is approved in accordance with this Code. This plan shows fixtures mounted at 20 feet. No alternative lighting plan has been provided. If you are going to propose alternative lighting plan, please include justification pursuant to LDC Sec. 6.2.3.E on the plan and in the letter of intent. | 1/4/2022 3:51:34 PM | |
PCD Project Manager
1/4/2022 3:44:09 PM |
Planning Division has the following comment on the landscape plan: Per previous comment: Request for alternative landscape with relation to internal landscape requirements may be needed. Please review LDC Sec. 6.2.2.A.4 and determine if an argument for alternative landscaping is needed. If so, please include justification on the landscape plan and in the letter of intent. This plan indicated 22 internal trees needed to meet requirement; however, none have been provided on the plan. | 1/4/2022 3:44:09 PM | |
EPC Stormwater Review
1/4/2022 4:50:01 PM |
Review 2: EPC Stormwater comments have been provided (in orange text boxes) on the following uploaded documents: - Drainage Report.....(to be uploaded by PM with PCD comments) - GEC Plan...............(to be uploaded by PM with PCD comments) - GEC Checklist EPC Stormwater comments have been resolved on the following documents: - Detention Maintenance Agreement - ESQCP - FAE - MS4 Post Construction Form - PBMP Applicability Form - SWMP Checklist - SWMP Please sign, date, and/or stamp the following docs as needed and resubmit: - GEC Plan - GEC Checklist (and add "PPR2147" to top of form) - ESQCP (and add "PPR2147" to top of form) - FAE - PBMP Applicability Form - SWMP Checklist (and add "PPR2147" to top of form) Reviewed by: Glenn Reese, P.E. Stormwater Engineer II glennreese@elpasoco.com |
1/4/2022 4:50:01 PM | |
View |
PCD Project Manager
10/22/2021 7:24:19 AM |
PCD Planning and PCD Engineering comments - site development plan | 10/22/2021 7:24:19 AM |
View |
PCD Project Manager
10/22/2021 7:23:29 AM |
PCD Planning comments - lighting plan | 10/22/2021 7:23:29 AM |
View |
PCD Project Manager
10/22/2021 7:23:13 AM |
PCD Planning comments - landscape plan | 10/22/2021 7:23:13 AM |
View |
PCD Project Manager
10/22/2021 7:22:51 AM |
EPC Stormwater comments - ESQCP | 10/22/2021 7:22:51 AM |
View |
PCD Project Manager
10/22/2021 7:22:33 AM |
PCD Engineering and EPC Stormwater comments - grading & erosion control plan | 10/22/2021 7:22:33 AM |
View |
PCD Project Manager
10/22/2021 7:22:19 AM |
PCD Engineering and EPC Stormwater comments - financial assurance forms | 10/22/2021 7:22:19 AM |
View |
PCD Project Manager
10/22/2021 10:50:13 AM |
PCD Engineering and EPC Stormwater comments - drainage report | 10/22/2021 10:50:13 AM |
PCD Engineering Division
10/21/2021 2:06:15 PM |
The project manager will upload any comments. Please address comments on the following documents: -Drainage report -Site development plan -Financial assurance form -Grading and erosion control plan Reviewed by: Lupe Packman Review Engineer lupepackman@elpasoco.com |
10/21/2021 2:06:15 PM | |
PCD Project Manager
10/22/2021 10:49:31 AM |
Planning Division has comments on the following documents: - Site development plan - Landscape plan - Lighting plan |
10/22/2021 10:49:31 AM | |
View |
EPC Stormwater Review
10/14/2021 11:45:48 AM |
SWMP_V1 | 10/14/2021 11:45:48 AM |
View |
EPC Stormwater Review
10/14/2021 11:45:12 AM |
SWMP Checklist_V1 | 10/14/2021 11:45:12 AM |
View |
EPC Stormwater Review
10/14/2021 11:44:59 AM |
PBMP Applicability Form_V1 | 10/14/2021 11:44:59 AM |
View |
EPC Stormwater Review
10/14/2021 11:44:47 AM |
MS4 Post Construction Form_V1 | 10/14/2021 11:44:47 AM |
View |
EPC Stormwater Review
10/14/2021 11:44:36 AM |
Grading & Erosion Control checklist_V1 | 10/14/2021 11:44:36 AM |
EPC Stormwater Review
10/14/2021 11:44:04 AM |
Review 1: EPC Stormwater comments have been provided (in orange text boxes) on the following uploaded documents: - Drainage Report...(to be uploaded by PM with PCD comments) - ESQCP...................(to be uploaded by PM with PCD comments) - FAE.......................(to be uploaded by PM with PCD comments) - GEC Plan...............(to be uploaded by PM with PCD comments) - GEC Checklist - MS4 Post Construction Form - PBMP Applicability Form - SWMP Checklist - SWMP Please upload the following documents separate from the MS4 Post Construction Form (ask the PM to open up slots for them): - Private Detention Basin / Stormwater Quality BMP Maintenance Agreement - SDI Reviewed by: Glenn Reese, P.E. Stormwater Engineer II glennreese@elpasoco.com |
10/14/2021 11:44:04 AM | |
Pikes Peak Regional Building Department
10/11/2021 3:12:40 PM |
1. Once the area is proposed to develop, the access road and address to the MVEA substation must change. The currently assigned address is 9167 Mohawk Road. 2. I permanent sign at the corner of Mohawk Road where is dead ends to the north, with the address to the substation will be required to be posted, pointing in the direction of the access road to the substation. 3. The address to the control building and above ground water tank will have separate addresses. Will these be built with the substation project at this time? Contact Enumerations if addresses are needed at this time. Amy Vanderbeek amy@pprbd.org 4. If the fencing does not exceed 7’, then an address and separate permit will not be required. Amy Vanderbeek Enumerations Plans Examiner Pikes Peak Regional Building Department O: 719-327-2930 E: Amy@pprbd.org W: 719-327-2953 |
10/11/2021 3:12:40 PM | |
Upper Black Squirrel Creek GWMD
10/6/2021 3:45:35 PM |
The Upper Black Squirrel Creek GWMD does not have any comments at this time but respectfully reserves the right to comment on any future submittals. | 10/6/2021 3:45:35 PM | |
911 Authority - El Paso/Teller County
9/27/2021 9:35:32 AM |
No new street names requested on this submittal. No action for E911. Thank you. Justin. |
9/27/2021 9:35:32 AM | |
Colorado Springs Utilities, Dev, Svc.(includes water resources)
9/22/2021 9:14:02 AM |
The review is complete. Approval is recommended. If gas services are needed, please reach out to our gas field engineering team at 719-668-4985. Regards ___________________________________________ Corey Masoumi | Engineering Support Coordinator Colorado Springs Utilities | Utilities Development Services PHYSICAL: 1521 S Hancock Expressway, Colorado Springs, CO 80903 MAILING: PO BOX 1103, MC 1812, Colorado Springs, CO 80947-0010 Direct (719) 668-1856 | Main (719) 668-8259 www.csu.org • www.csu.org/Pages/BuildingDevelopment.aspx |
9/22/2021 9:14:02 AM | |
View |
EPC Health Department
9/21/2021 7:41:59 PM |
9/21/2021 7:41:59 PM | |
Academy SD 20 Building Fund
9/21/2021 7:14:56 AM |
Academy District 20 is in receipt of File# PPR2147 for approval of the Volmer-Volmer Tap kV Transmission Substation SDP. The District has no comment regarding the approval of the Volmer-Volmer Tap kV Transmission Substation SDP. Don Smith Planning Consultant |
9/21/2021 7:14:56 AM | |
Black Forest Fire Protection District
9/20/2021 3:35:54 PM |
Black Forest Fire Rescue This project appears to be in the Falcon Fire Protection District. There a re no comments by BFFR. |
9/20/2021 3:35:54 PM |