PCD Engineering Division
6/19/2023 8:44:28 AM |
Previous review comments have been resolved. There are no further comments relating to drainage or transportation at this time. Any approved documents will be uploaded by the project manager. Reviewed by: Carlos Hernandez Review Engineer carloshernandez@elpasoco.com |
6/19/2023 8:44:28 AM | |
PCD Engineering Division
5/30/2023 12:57:51 PM |
Review 1: In the "Narrative for Zoning Review" please include the size of the concrete pad and amount of grading anticipated for the concrete pad and generator. Please also include a statement confirming the proposed work will not adversely impact drainage or adjacent properties. FYI: It is the applicant's responsibility to ensure compliance with any state regulations regarding fuel storage and spill cleanups for the proposed diesel generator. Reviewed by: Carlos Hernandez Review Engineer carloshernandez@elpasoco.com |
5/30/2023 12:57:51 PM |