View: Project Documents
Agency | Comment | ||
---|---|---|---|
County Attorney - Development Review
11/18/2020 10:17:23 PM |
No further comments from County Attorney's Office. | 11/18/2020 10:17:23 PM | |
PCD Engineering Division
11/8/2020 6:07:07 PM |
Engineering documents have been approved on 11/6/2020. EN |
11/8/2020 6:07:07 PM | |
County Attorney - Development Review
11/5/2020 4:30:04 PM |
The Detention Maintenance Agreement is acceptable. The signed pdf of the Agreement submitted, however, is the redlined draft from my review. Please make sure the signed pdf has all changes accepted and does not show any redlines, then resubmit. | 11/5/2020 4:30:04 PM | |
View |
Colorado Department of Transportation - Pueblo Office
11/2/2020 10:57:49 AM |
11/2/2020 10:57:49 AM | |
PCD Engineering Division
10/27/2020 9:19:21 AM |
Review comments provided by: Jack Patton jackpatton@elpasoco.com (719) 520-7951 Engineering comments have been resolved. Please submit signed engineering documents for approval by the ECM administrator. |
10/27/2020 9:19:21 AM | |
View |
County Attorney - Development Review
10/26/2020 2:09:56 PM |
A couple of minor changes to the Detention Maintenance Agreement are attached. | 10/26/2020 2:09:56 PM |
EPC Stormwater Review
10/19/2020 12:42:50 PM |
Review 3: EPC Stormwater comments have been resolved on the following documents: - GEC Checklist - GEC Plan - SWMP Checklist - SWMP No further comments by EPC Stormwater at this time. Reviewed by: Glenn Reese, P.E. Stormwater Engineer I glennreese@elpasoco.com |
10/19/2020 12:42:50 PM | |
View |
PCD Project Manager
10/9/2020 9:48:45 AM |
See engineering comments on GEC plan. | 10/9/2020 9:48:45 AM |
View |
PCD Project Manager
10/9/2020 9:48:15 AM |
See comments on site development plan from engineering and PM that were not addressed from previous submission. | 10/9/2020 9:48:15 AM |
PCD Engineering Division
10/8/2020 4:46:28 PM |
Review comments provided by: Jack Patton jackpatton@elpasoco.com (719) 505-0236 Please see engineering comments provided on the following documents uploaded by the project manager: - Site Development Plan - GEC The northern access point will need to be closed during phase II of construction. Review I comments were not addressed on the site development plan: Per ECM 2.4.1.B, this does not meet the access spacing requirements for two access points. This access will need to be closed upon completion of Phase I construction and included in Phase II of construction. DPW constructed the entryway improvements for the continued operation of the existing firehouse. When the Fire Department moves into the new building, the access will no longer be needed for fire trucks and shall be closed permanently. |
10/8/2020 4:46:28 PM | |
County Attorney - Development Review
10/6/2020 9:52:04 PM |
Exhibit A to the Detention Maintenance Agreement must be a legal description of the subject property, not a copy of the plat, i.e. Lot 1, Falcon Fire Protection District Station No. 3 Exemption Plat. Typically with site plans, an easement is granted to the County across the property in Exhibit A to provide for access to and inspection of the detention pond. If applicant wishes to proceed this way, Exhibit B should be deleted, and any reference to Exhibit B in the Agreement should be changed to Exhibit A. If applicant wishes to grant the County an easement across less than entire property in Exhibit A, the applicant must prepare a legal description and depiction of such easement, not attached the GEC plan. The easement must abut a public right-of-way to permit access to the detention pond. |
10/6/2020 9:52:04 PM | |
View |
EPC Stormwater Review
10/5/2020 1:02:03 PM |
SWMP_v2 | 10/5/2020 1:02:03 PM |
View |
EPC Stormwater Review
10/5/2020 1:01:43 PM |
SWMP Checklist_v2 | 10/5/2020 1:01:43 PM |
View |
EPC Stormwater Review
10/5/2020 1:01:16 PM |
Grading and Erosion Control Plan_v2 | 10/5/2020 1:01:16 PM |
View |
EPC Stormwater Review
10/5/2020 1:00:46 PM |
Grading and Erosion Control Checklist_v2 | 10/5/2020 1:00:46 PM |
EPC Stormwater Review
10/5/2020 1:00:16 PM |
Review 2: EPC Stormwater comments have been provided on the following uploaded documents: - GEC Checklist - GEC Plan - SWMP Checklist - SWMP EPC Stormwater comments have been resolved on the following documents: - FAE Reviewed by: Glenn Reese, P.E. Stormwater Engineer I glennreese@elpasoco.com |
10/5/2020 1:00:16 PM | |
Colorado Department of Transportation - Pueblo Office
9/30/2020 5:48:19 PM |
Comments will be forthcoming. | 9/30/2020 5:48:19 PM | |
View |
Colorado Department of Transportation - Pueblo Office
8/21/2020 4:00:02 PM |
8/21/2020 4:00:02 PM | |
View |
EPC Parks Department
8/20/2020 3:43:29 PM |
See Parks comments attached. | 8/20/2020 3:43:29 PM |
Woodmen Hills Metro
8/20/2020 12:53:36 PM |
Woodmen Hills Metropolitan District offers no comments at this time. | 8/20/2020 12:53:36 PM | |
Falcon Highlands Metro
8/20/2020 11:05:08 AM |
Falcon Highlands Metropolitan District has no objections to this project. Please note that no trees can be planted within 5 feet of any utilities owned by FHMD or Woodmen Hills Metropolitan District. | 8/20/2020 11:05:08 AM | |
Upper Black Squirrel Creek GWMD
8/19/2020 2:53:41 PM |
The Upper Black Squirrel Creek GWMD does not have any comments at this time but reserves the right to comment in the future. | 8/19/2020 2:53:41 PM | |
View |
PCD Project Manager
8/19/2020 8:17:04 AM |
Site Development Plan Redlines | 8/19/2020 8:17:04 AM |
View |
PCD Project Manager
8/19/2020 8:16:40 AM |
Lighting Plan Redlines | 8/19/2020 8:16:40 AM |
View |
PCD Project Manager
8/19/2020 8:15:20 AM |
Letter of Intent Redlines | 8/19/2020 8:15:20 AM |
View |
PCD Project Manager
8/19/2020 8:14:53 AM |
Landscape Plan Redlines | 8/19/2020 8:14:53 AM |
View |
PCD Project Manager
8/19/2020 8:14:28 AM |
GEC Plan Redlines | 8/19/2020 8:14:28 AM |
View |
PCD Project Manager
8/19/2020 8:14:10 AM |
GEC Checklist Redlines | 8/19/2020 8:14:10 AM |
View |
PCD Project Manager
8/19/2020 8:13:44 AM |
Financial Assurance Redlines | 8/19/2020 8:13:44 AM |
View |
PCD Project Manager
8/19/2020 8:13:19 AM |
Drainage Report Redlines | 8/19/2020 8:13:19 AM |
PCD Engineering Division
8/18/2020 10:08:28 AM |
Review comments provided by: Jack Patton jackpatton@elpasoco.com (719) 505-0236 Please see the engineering comments on the following documents uploaded by the project manager: - Drainage Report - Financial Assurance Estimate Form - Grading and Erosion Control Plan/Checklist - Site Development Plan Missing Required Documents: - Pond O&M Manuals - SDI Worksheet - MS4 Post Construction - Non Jurisdictional Impoundment Structure Form - Soils/Geology Report Driveway access permits are required for all access points. Can be applied for on EDARP under the "initiate a minor permit" link. |
8/18/2020 10:08:28 AM | |
Pikes Peak Regional Building Department
8/17/2020 8:09:30 AM |
NO FURTHER COMMENT. | 8/17/2020 8:09:30 AM | |
View |
EPC Health Department
8/15/2020 8:00:05 PM |
8/15/2020 8:00:05 PM | |
County Attorney - Development Review
8/5/2020 9:51:07 PM |
No changes to Detention Maintenance Agreement at this time. Please add exhibits for review. | 8/5/2020 9:51:07 PM | |
View |
EPC Stormwater Review
8/5/2020 8:31:46 AM |
SWMP_v1 | 8/5/2020 8:31:46 AM |
View |
EPC Stormwater Review
8/5/2020 8:31:26 AM |
SWMP Checklist_v1 | 8/5/2020 8:31:26 AM |
View |
EPC Stormwater Review
8/5/2020 8:30:46 AM |
Grading and Erosion Control Plan_v1 | 8/5/2020 8:30:46 AM |
View |
EPC Stormwater Review
8/5/2020 8:30:28 AM |
Grading and Erosion Control Checklist_v1 | 8/5/2020 8:30:28 AM |
View |
EPC Stormwater Review
8/5/2020 8:30:09 AM |
Financial Assurance Form_v1 | 8/5/2020 8:30:09 AM |
EPC Stormwater Review
8/5/2020 8:29:47 AM |
Review 1: Stormwater comments have been provided on the following uploaded documents: - FAE - GEC Checklist - GEC Plan - SWMP - SWMP Checklist Reviewed by: Glenn Reese, P.E. Stormwater Engineer I glennreese@elpasoco.com |
8/5/2020 8:29:47 AM | |
Colorado Springs Utilities, Dev, Svc.(includes water resources)
8/4/2020 3:23:47 PM |
Hey Petra, I have finished with the review for the subject application and have no action items at this time. A recommendation to contact CSU Field Engineer to ensure that there are no problems, but that is not a requirement. Approval can be recommended. Let me know if you need anything else from me. Thanks, Ryne |
8/4/2020 3:23:47 PM | |
View |
EPC Environmental Services
8/4/2020 11:32:44 AM |
8/4/2020 11:32:44 AM | |
View |
Mountain View Electric Association, Inc.
8/3/2020 9:29:12 AM |
8/3/2020 9:29:12 AM | |
Falcon Fire Protection District
8/3/2020 8:32:48 AM |
Falcon Fire has reviewed this development plan for a new fire station and administration building to be located at 7030 and 7020 Old Meridian Road. This site is currently has a full service fire station build in 1980. Fire has no objections or concerns with the development plan as currently proposed. No additional review required by Falcon Fire. | 8/3/2020 8:32:48 AM |